Fixed commercial gas detectors monitoring hydrogen (H2), carbon monoxide (CO) and/or nitrogen dioxide (NO2) for controlling Car Park Ventilation Systems in conjunction with the CH-S or CH-M Control Hubs.
CO and NO2 sensors are UL 2075 certified, ensuring that gas and vapor detectors are reliable, accurate, and can detect the presence of harmful gases in a timely manner.
Capable of housing one or two sensors offering flexibility, allowing precise monitoring of a specific gas with one sensor or simultaneous detection of two gases with enhanced safety and efficiency.
Monitors a sizable area, up to 7,500 sq. ft., providing extensive coverage for enhanced safety and early detection of hazardous gases.
Offers the flexibility to connect up to 4 sensors per CH-S Control Hub and 30 sensors per CH-M Control Hub. Add sensors at any time, allowing for easy scalability as monitoring needs evolve.
Streamlines the installation process with daisy chain power and communication, along with factory calibration and customized programming, reducing setup time and complexity.
Provides resilience against weather elements with rainproof water resistance and offers straightforward service and maintenance procedures, ensuring long-term reliability.
RD Series Remote Detectors | |
Input power (Single sensor) | 24 VAC, 50/60 Hz. 0.2A to 0.35A |
Power consumption (Single sensor) | 4.8 VA |
Power consumption (Dual sensor) | 8.5 VA |
Analog output | User-selectable 4-20 mA, 0.2-1 VDC, 1-5 VDC, or 2-10 VDC with zero offset enable/disable |
Digital communication | Modbus RTU |
Storage temperature | -58°F to 248°F (-50°C to 120°C) |
Humidity | 15% to 90% (non-condensing) |
Front panel indicators | 2 LEDs, Power (green), Fault (yellow) |
Dimensions | 4.98” W x 4.98” H x 2.18” D (12.6 cm W x 12.6 cm H x 5.5 cm D) |
Weight | 1 lb (0.5 kg) |
Housing | Gray, NEMA 3R, polycarbonate plastic |
Performance (CO/NO2 only) | ANSI/ISA 92.00.01-2010 (R2015) |
Electromagnetic interference | EN 50270, FCC Part 15 Subpart B |
Environmental | RoHS |
CO | NO2 | H2 | |
Model (Item #) | RD-CO (#494104) | RD-NO2 (#494105) | RD-H2 (#494130) |
Performance range | 0-200 PPM | 0-10.0 PPM | 0-100% LEL |
Performance resolution | 1 PPM | 0.1 PPM | 1% LEL |
Calibration point | 100 PPM | 5.0 PPM | 50% LEL |
Maximum overload | 2,000 PPM | 200 PPM | n/a |
T90 response time | < 30 seconds | < 50 seconds | < 20 seconds |
Coverage radius | 50 ft. | 50 ft. | 40 ft. |
Coverage area | 7,500 sq. ft. | 7,500 sq. ft. | 5,000 sq. ft. |
Sensor type | Electromechanical | Electromechanical | Catalytic bead |
Long term output drift | < 5% per year | < 2% per year | < 5% per year |
Expected sensor life | > 7 Years | > 5 Years | 2 Years |
Calibration duration | 2 Years | 1 Year | n/a |
Note: RD-Dual (#494106) combines a CO and NO2 sensors into one remote detector. |