RD

RD

Fixed commercial gas detectors monitoring hydrogen (H2), carbon monoxide (CO) and/or nitrogen dioxide (NO2) for controlling Car Park Ventilation Systems in conjunction with the CH-S or CH-M Control Hubs.

UL 2075 Certified

CO and NO2 sensors are UL 2075 certified, ensuring that gas and vapor detectors are reliable, accurate, and can detect the presence of harmful gases in a timely manner.

Single or Dual Sensor Configurations

Capable of housing one or two sensors offering flexibility, allowing precise monitoring of a specific gas with one sensor or simultaneous detection of two gases with enhanced safety and efficiency.

Excellent Coverage

Monitors a sizable area, up to 7,500 sq. ft., providing extensive coverage for enhanced safety and early detection of hazardous gases.

Seamless Expansion

Offers the flexibility to connect up to 4 sensors per CH-S Control Hub and 30 sensors per CH-M Control Hub. Add sensors at any time, allowing for easy scalability as monitoring needs evolve.

Simplified Installation

Streamlines the installation process with daisy chain power and communication, along with factory calibration and customized programming, reducing setup time and complexity.

Enhanced Durability

Provides resilience against weather elements with rainproof water resistance and offers straightforward service and maintenance procedures, ensuring long-term reliability.

Technical Specifications

RD Series Remote Detectors
Input power (Single sensor)24 VAC, 50/60 Hz. 0.2A to 0.35A
Power consumption (Single sensor)4.8 VA
Power consumption (Dual sensor)8.5 VA
Analog outputUser-selectable 4-20 mA, 0.2-1 VDC, 1-5 VDC, or 2-10 VDC with zero offset enable/disable
Digital communicationModbus RTU
Storage temperature-58°F to 248°F (-50°C to 120°C)
Humidity15% to 90% (non-condensing)
Front panel indicators2 LEDs, Power (green), Fault (yellow)
Dimensions4.98” W x 4.98” H x 2.18” D (12.6 cm W x 12.6 cm H x 5.5 cm D)
Weight1 lb (0.5 kg)
HousingGray, NEMA 3R, polycarbonate plastic
Performance (CO/NO2 only)ANSI/ISA 92.00.01-2010 (R2015)
Electromagnetic interferenceEN 50270, FCC Part 15 Subpart B
EnvironmentalRoHS

Sensor Performance

CONO2H2
Model (Item #)RD-CO (#494104)RD-NO2 (#494105)RD-H2 (#494130)
Performance range0-200 PPM0-10.0 PPM0-100% LEL
Performance resolution1 PPM0.1 PPM1% LEL
Calibration point100 PPM5.0 PPM50% LEL
Maximum overload2,000 PPM200 PPMn/a
T90 response time< 30 seconds< 50 seconds< 20 seconds
Coverage radius50 ft.50 ft.40 ft.
Coverage area7,500 sq. ft.7,500 sq. ft.5,000 sq. ft.
Sensor typeElectromechanicalElectromechanicalCatalytic bead
Long term output drift< 5% per year< 2% per year< 5% per year
Expected sensor life> 7 Years> 5 Years2 Years
Calibration duration2 Years1 Yearn/a
Note: RD-Dual (#494106) combines a CO and NO2 sensors into one remote detector.