High-performing smoke extract fans for harsh working conditions in the event of a fire
Continuous medium temperature up to 200°C
Smoke extraction 400°C/2h (F400)
Acoustic and thermal insulation 50 mm
Easy to service and maintain due to the swing-out inspection door
The smoke extract units KBR/F are used in case of fire to extract smoke gases and also during normal working conditions for temperature up to 200°C continuously.
The KBR casing is manufactured from double skinned galvanised sheet steel and is insulated with 50mm mineral wool.
High-performance impeller together with highly efficient motors are designed to ensure high-level performance to minimise power consumption and maximise efficiency.
The KBR/F casing is manufactured from double skinned galvanised sheet steel and is insulated with 50 mm mineral wool.
The fan is isolated from the casing via connectors and anti-vibration dampers are incorporated into the base frame. Standard is that the motor is outside the air stream.
The KBR/F fans have a swing-out door for easy inspection and service.
Tested according to EN 12101- 3. CE Certification according to EN 12101-3; 2002-06 through TÜV Süd.
The KBR/F fans use radial impeller with backward curved blades. These are made out of aluminium, dynamically balanced and paired with corresponding IEC motor with efficiency IE3 or EC motor.
High-temperature motors for temperature classification F400 (400°C/120 min).
Fans with AC motors have an integrated thermal protection with manual (electrical) reset, thermistor PTC for connection to a motor protection device.
Fans with EC motors have an integrated electronic thermal protection including locked-rotor protection and soft-start.
The AC motors can be controlled by 5-step, stepless speed regulator, D/Y switch or frequency converter.
EC motors with built-in potentiometer to adjust working point can be also controlled by external signal 0-10V.
The fans can be used indoor or with specific accessories also outdoor. Due to the mounted base frame the fan can stand on floor.
400V 3~ 50Hz | |||
---|---|---|---|
Nominal data | |||
Voltage (nominal) | 400 | V | |
Frequency | 50 | Hz | |
Phases | 3~ | ||
Input power | 1,215 | W | |
Input power kW | 1.215 | kW | |
Starting current | 22.4 | A | |
Input current | 2.18 | A | |
Impeller speed | 2,940 | rpm | |
Air flow | max 1.146 | m³/s | |
Max. Temperature of transported air for 120 min | 400 | °C | |
Temperature of transported air | max 200 | °C | |
Max temperature of transported air, when speed controlled | 200 | °C | |
Sound data | |||
Sound pressure level at 10m (free field) | 42 | dB(A) | |
Sound pressure level at 4m (free field) | 50 | dB(A) | |
Protection/Classification | |||
Enclosure class, motor | IP55 | ||
Insulation class | F | ||
Dimensions and weights | |||
Duct dimension; Circular, inlet | 315 | mm | |
Weight | 65.2 | kg | |
Others | |||
Motor type | AC |