SUE250EC 9kW

SUE Air Handling Units

Air Handling Unit suitable for a range of settings

  • Low Sound 

  • Compact Design 

  • Integrated Motor Protection 

  • Flexible Installation


SUE 250EC 9kW#94729
Frequency: 50 Hz
On demand
or create account to buy online

Flexible Installation

The SUE air handling unit features a plug-and-play electrical connection and flexible installation on site for existing buildings.


High Efficiency

The SUE air handling unit features a highly efficient EC fan. The fan can be controlled via a 5-step switch. 


Easy Cleaning

The intelligent design of the SUE air handling unit enables fast, easy cleaning and servicing to ensure optimal performance and longevity. 


The SUE air handling unit is designed for flexible, straightforward installation and efficient operation. With its compact design, it is suitable for installation and use in a range of settings. The unit features revision doors for straightforward revision and service work. The intelligent design of the unit, along with EC fans, enables easy cleaning. 

The fan is controllable via a 5-step switch. The temperature controller is pre-adjusted at 20°C. The unit features integrated motor protection. The SUE air handling unit has 30mm thick panels with mineral wool insulation to ensure a low sound operation. This makes it suitable for installation in a variety of settings. The unit has a changeable filter (ePM1 60%/F7). The SUE air handling unit has low SFP values and high efficiency.

Tech specs

Technical Data

Article name
SUE 250EC 9kW
Trade name
Systemair
Article number
#94729
9kW
Unit
Frequency50Hz
Voltage (nominal)400V
Phases3~
Speed regulationStepless
Air flowmax 408L/s
Note: Separate power supply
Motor typeEC
Supply fan
Voltage230V
Phases1~
Current1.34A
Input power (P1), supply fan164W
Impeller speed2,670rpm
Temperature of transported airmax 50°C
Insulation classB
Enclosure class, motorIP44
Supply air filter
Filter class, supply airePM1 60%
Heater
Voltage400V
Phases3~
Current, electrical heating battery14.34A
Input power, heater9kW
Dimensions and weights
Weight55kg
Sound data
Sound pressure level at 3m (20m² Sabin)48dB
ERP
ErP readyErP 2018

Ecodesign

9kW
Other
ErP compliance2018
Unit categoryNRVU
DriveExternal MSD or VSD
Unit typeUVU
Heat recovery typeNone
Temperature ratio (UVU)Not applicable
qv nom0.1717m³/s
P nom0.067kW
Ps nom105Pa
Fan efficiency26.9%
Sound power (LWA)56dB(A)

Performance

Dimensions

SUE #94729, Dimensions
      
A
□ BØCØDEF
1019
5202502506437

Documentation