Self-adjusting exhaust vent suitable for kitchens, bathrooms, and toilets
Self Adjusting
Fixed Flow
Silencer Module
Attractive Design
AL is a self-adjusting exhaust vent featuring fixed flow for use in central ventilation systems.
AL has an aerodynamic design and provides a perfect match between high technical performances and aesthetic requirements.
The AL airflow element is a rigid flap that provides a pre-determined extraction flow between 50-150 Pa.
The AL self-adjusting exhaust vent provides a perfect match between high technical performances and aesthetic requirements. AL features fixed flow and provides uniform architectural solutions to kitchen, bathroom, and WC ventilation problems. The airflow element is a rigid flap that provides a pre-determined extraction flow between 50-150 Pa.
The AL has an intelligent design, is executed in white polystyrene, and features mounting rings in diameter 100 or 125 mm, plastic renovation plates, and a silencer module.
Default | |||
---|---|---|---|
Product | |||
Air flow, max [m³/h] | 8 | L/s | |
Dimensions and weights | |||
Weight | 0.14 | kg |
AL with | Lw en dB(A) | Dn,e,w (C) | ||||
silencer module | 70 Pa | 100 Pa | 130 Pa | 160 Pa | dB | |
15/30 m³/h | 27 | 30 | 33 | 36 | 64 | |
20/75 m³/h | 26 | 30 | 32 | 34 | 64 | |
30/90 m³/h | 27 | 31 | 34 | 37 | 63 | |
45/135 m³/h | 28 | 31 | 34 | 36 | 62 |
AL with | Lw en dB(A) | Dn,e,w (C) | ||||
silencer module | 70 Pa | 100 Pa | 130 Pa | 160 Pa | dB | |
15 m³/h | 19 | 27 | 31 | 34 | 64 | |
30 m³/h | 27 | 30 | 33 | 36 | 64 | |
45 m³/h | 28 | 31 | 34 | 36 | 62 |
AL | Lw en dB(A) | Dn,e,w (C) | ||||
70 Pa | 100 Pa | 130 Pa | 160 Pa | dB | ||
15/30 m³/h | 27 | 30 | 33 | 36 | 59 | |
20/75 m³/h | 24 | 27 | 30 | 33 | 56 | |
30/90 m³/h | 25 | 31 | 34 | 36 | 56 | |
45/135 m³/h | 27 | 33 | 34 | 37 | 55 | |
AL | Lw en dB(A) | Dn,e,w (C) | ||||
70 Pa | 100 Pa | 130 Pa | 160 Pa | dB | ||
15 m3/h | 19 | 27 | 31 | 34 | 60 | |
30 m3/h | 27 | 30 | 33 | 36 | 59 | |
45 m³/h | 27 | 33 | 34 | 37 | 55 |
Vents characterized by their standard noise attenuation qualities Dn,e,w (C) and their acoustic power level Lw (at a stable extraction flow) measured in compliance with the specificationin pr EN 13141-2.
The sound pressure level due to the vents own noise is given by the formula:
Lp = Lw - 10 log (V/12,5) in dB(A) where V is the volume of the room in m
3
Example: for a 40 m
3
room, and Lw = 31 dB(A), Lp = 26 dB(A).
Noise attenuation Dn,e,w (C) is determnined using the Ø 125 sleeve, the opening being fitted with or without a silencer module.