TFE 220 M Vent.de tejado #1269
Speed controllableTilting mechanism for easy servicingMaintenance-free and reliableVertical exhaustThe TFE 220 has an impeller with backward-curved blades and maintenance-free external rotor motors. The casing is manufactured in powder-coated, galvanised sheet steel in the standard colours of black or brick red. These fans have integral mains circuit-breakers, and have a tilting mechanism for easy inspection and servicing. Exhaust air is directed vertically from the fans, which prevents problems caused by wet snow and staining of the roof. To protect the motor from overheating, the TFE 220 has integral thermal contacts with electrical reset. These fans are suitable for use in exhaust-air ventilation systems, in single and multiple dwellings, offices and day nurseries.
Cumple las normas y requisitos actuales y futuros de la Unión Europea en materia de etiquetado energético y diseño ecológico de productos relacionados con la energía (ErP).
230V 1~ 50Hz | |||
---|---|---|---|
Datos nominales | |||
Tensión (nominal) | 230 | V | |
Frecuencia | 50 | Hz | |
Fases | 1~ | ||
Potencia de entrada | 107 | W | |
Potencia de entrada kW | 0,107 | kW | |
Corriente de entrada | 0,468 | A | |
Revoluciones por minuto | 2.602 | rpm | |
Caudal de aire | máximo 788 | m³/h | |
Capacidad del condensador | 3 | µF | |
Temperatura del aire transportado | máximo 70 | °C | |
Temperatura maxima del aire transportado, con velocidad controladoa | 70 | °C | |
Datos de ruido | |||
Nivel de presion sonora a 10m (campo abierto) | 38 | dB(A) | |
Protección/Clasificación | |||
Clase de protección, motor | IP44 | ||
Clase de aislamiento | B | ||
Datos de acuerdo a ErP | |||
Clase energetica, unidad basica | E | ||
Clase energetica, demanda local | B | ||
ErP listo | ErP 2016; ErP 2018 | ||
Dimensiones y pesos | |||
Peso | 8 | kg | |
Otros | |||
Color de la carcasa | Negro | ||
Tipo de motor | AC |
230V 1~ 50Hz | |||
---|---|---|---|
Producto | |||
Nombre comercial | Systemair | ||
Nombre del preducto | TFE 220 M Roof fan | ||
Unidad básica | |||
Conformidad ErP | 2016 | ||
Promedio SEC | -13,1 | kWh/(m².a) | |
SEC frío | -29,5 | kWh/(m².a) | |
SEC calor | -3,7 | kWh/(m².a) | |
SEC clase | E | ||
Categoriade unidad | RVU | ||
Tipo de unidad | UVU | ||
Conducir | MSD externa o VSD | ||
Tipo de recuperacion de calor | Ninguno | ||
Proporcion de temperatura (UVU) | N / A | ||
QV máx. | 644 | m³/h | |
P max | 100 | W | |
Potencia acústica (LWA) | 57 | dB(A) | |
ref QV | 0,125 | m³/s | |
PS ref | 50 | Pa | |
SPI | 0,128 | W/(m³/h) | |
CTRL | 1 | ||
MISC | 1,1 | ||
valor de x | 1,5 | ||
Fuga externa | 0 | % | |
Consumo eléctrico anual medio | 160,3 | kWh | |
Consumo de calefacción ahorrado en refreigeración | 160,3 | kWh | |
Consumo eléctrico anual en calefacción | 160,3 | kWh | |
AHS Medio | 1.715,2 | kWh/a | |
Consumo de calefacción ahorrado en calefacción | 775,6 | kWh/a | |
Unidades con control de demanda local | |||
Conformidad ErP | 2018 | ||
Promedio SEC | -26,2 | kWh/(m².a) | |
SEC frío | -53,3 | kWh/(m².a) | |
SEC calor | -10,7 | kWh/(m².a) | |
SEC clase | B | ||
Categoriade unidad | RVU | ||
Tipo de unidad | UVU | ||
Conducir | MSD externa o VSD | ||
Tipo de recuperacion de calor | Ninguno | ||
Proporcion de temperatura (UVU) | N / A | ||
QV máx. | 645 | m³/h | |
P max | 100 | W | |
Potencia acústica (LWA) | 57 | dB(A) | |
ref QV | 0,1254 | m³/s | |
PS ref | 50 | Pa | |
SPI | 0,128 | W/(m³/h) | |
CTRL | 0,65 | ||
MISC | 1,1 | ||
valor de x | 1,5 | ||
Fuga externa | 0 | % | |
Consumo eléctrico anual medio | 84 | kWh | |
Consumo eléctrico anual en refrigeración | 84 | kWh | |
Consumo eléctrico anual en calefacción | 84 | kWh | |
AHS Medio | 2.830 | kWh/a | |
Consumo de calefacción ahorrado en refreigeración | 5.536,2 | kWh/a | |
Consumo de calefacción ahorrado en calefacción | 1.279,7 | kWh/a |