SYSVRF3 DUCT 112 Q #455454
Jõudlused | |||
---|---|---|---|
Power input heating | 15.5 | kW | |
Jahutusvõime | 11.2 | kW | |
Power input | 138 | W | |
Max. operation current | 2.29 | A | |
Soovitatav kaitse | 15 A | ||
Üldandmed | |||
Air volume [m³/h] | 1950/1817 /1683/1550/1417/1283/1150 | ||
External pressure | 40 (10-160) Pa | ||
Külmaaine tüüp | R410A / R32 | ||
Power supply | 230V/ 1~Ph /50Hz | ||
Sagedus | 50 | Hz | |
Faasid | 1~ | ||
Air volume | 1950/1817 /1683/1550/1417/1283/1150 | ||
Keskkonna töötemperatuuri vahemik jahutusel | +17…+32°C | ||
Keskkonna töötemperatuuri vahemik küttel | +10…+28°C | ||
Dimension liquid pipe | 9,52 (3/8”) | ||
Dimension gas pipe | 15,9 (5/8”) | ||
Dimension (WxHxD) | 1,510 x 245 x 770 | ||
Dimension packing (WxHxD) | 1,565 x 305 x 890 | ||
Drain pipe | OD 25 | ||
Design pressure (H/L) (bar) | 44/15 | ||
Müra andmed | |||
Sound pressure level dB(A) | 39/37/35/33/31/29/28 | ||
Sound power level dB(A) | 60/58/56.5/55 /53.5/52/50 | ||
Mõõtmed ja kaal | |||
Kõrgus | 245 | mm | |
Sügavus | 770 | mm | |
Laius | 1 510 | mm | |
Kaal | 37 | kg | |
Nominal conditions | |||
Indoor unit cooling | 27°C DB, 19°C WB | ||
Indoor unit heating | 20°C DB, 15°C WB |