MRH400-2-1.1-F400

MRH Tourelles

MRH 400-2-1.1-F400#9995300
Fréquence: 50 Hz
ou créer un compte pour acheter en ligne

Certifications

Chargement en cours...

Spécifications techniques

Données techniques

Nom de l'article
MRH 400-2-1.1-F400
Numéro d'article
#9995300
400V 3~ 50Hz - Y (Star)
Données nominales
Tension (nominale)400V
Fréquence50Hz
Phases3~
Puissance installée1'313W
Puissance d'entrée kW1.313kW
Puissance nominale à l'axe (P2)1.1kW
Intensité2.4A
Vitesse de rotation2'940rpm
Débit d'airmax 7'100m³/h
Température d'air maximum pendant 120mn400°C
Température air en mouvement-20 à 55°C
Données acoustique
Niveau sonore à 10 m61dB(A)
Niveau sonore à 3 m (champ libre)71dB(A)
Niveau sonore à 4 m (champ libre)69dB(A)
Protection/Classification
Classe d'étanchéitéIP55
Classe d'étanchéité, moteurIP55
Classe d'isolationH
CertificatCPR 597958
Standard EUEN 12101-3
Données selon ErP
Conformité ErPPas d'ErP pertinent
Dimensions et Poids
Conduit Circul d'aspiration400mm
Poids259kg
Autres
Type de connexionCirculaire
Type de moteurAC

Logiciel de sélection

Dimensions

MRH #9995300, Dimensions
TypeøDøD1n x M*AA1A2BB1B2GCHFHH1SH, ~SV, ~
MRH-AXC 400
4004508 x M8*1000747107010007471050106445012501410185800
*bolts

Documentation technique

Câblage

MRH #9995300, Câblage
MRH #9995300, Câblage
Diagram 1 (connection of electric motor in the fan`s service switch)
Electric motor with P2<=4 kW in Y or D connection
Lock the switch in position ON to prevent unintended switch OFF (lock is not in scope of delivery)
Diagram 2 (connection of actuator in the actuator`s service switch)
* 24VDC (+30/-20%)
** NO/NC are intended to control position of actuator`s service switch (ON - OFF)
Warning: the control voltage 24VDC to open or close hatch cover should apply max. 6 minutes.
This is to ensure by control system (use actuator`s internal floating limit switches as indication of cover position to cut off the control voltage). More see instructions (current, intermittence).
The connection cable to service switch calculate with max. 1V voltage drop at max. load!
Operating mode for peak load at 25°C ambient: S2 1 min
Operating mode for continuous load at 40°C ambient: S3 5% (example: open in 30s, then wait 9min 30s)
Max. current of actuator(s) at SL 1000 (rated MRH load):
MRH 400-630: 4A
MRH 710-800: 6A
MRH 1000: 8A
MRH 1120-1250: 2x8A=16A
Diagram 3 (connection of actuator`s internal floating limit switches in the actuator`s service switch)
*** drawn position - closed hatch
1-2 opened, 2-3 closed in closed hatch position
1-2 closed, 2-3 opened in opened hatch position
1-2 closed, 2-3 closed in any intermediary position of the hatch cover
1-2, 4-5 opened, 2-3, 5-6 closed in closed hatch position (MRH 1120-1250 only)
1-2, 4-5 closed, 2-3, 5-6 opened in opened hatch position (MRH 1120-1250 only)
1-2, 4-5 closed, 2-3, 5-6 closed in any intermediary position of the hatch cover (MRH 1120-1250 only)
Potentialfree NC contacts, load capacity 24VDC/1A
Functions of the actuator`s service switch:
Position 0: stop (NO - opened contact, NC - closed contact) - SAFETY POSITION
Position 1: open hatch cover (NO - closed contact, NC - opened contact) - WARNING!
Position 2: close hatch cover (NO - opened contact, NC - closed contact) - DANGER!