MRH400-2-1.1-F400
01000200030004000500060007000m³/h0100200300Pa
Išplėstinis skaičiavimas

MRH Stoginiai ventiliatoriai

MRH 400-2-1.1-F400#9995300
Dažnis: 50 Hz
6.940,00 €neįskaitant mokesčių
arba sukurti paskyrą norėdami pirkti

MRH 400-2-1.1-F400 #9995300

MRH roof hatch with axial fan for smoke and heat extraction •    Version for installation on flat roof •    Vertical exhaust•    Certified for insertion of axial fan with motor inside air stream•    Tested to F400 (400°C/2h) requirement up to EN 12101-3•    SL 1000 respectively SL 1250 at size 1250 (EN 12101-3)•    WL 1500 (EN 12101-2), wind suction load•    CPR certificate by BSI (EU and UK)•    Insulation thickness: walls 120 mm, cover 150 mm•    Thermal transmittance class T2•    Electrically operated spindle actuator for hatch cover opening•    Serially equipped with power supply 230V AC --> 24V DC for actuators of hatch cover•    Indication for opened/closed hatch cover position (switches)•    Robust structure•    Sucking side connection acc. Eurovent 1/2•    Exhaust protective grid is included•    On request: F300 fans, decorative painting, supply/pressurisation unit, without fanMRH, motorised roof hatch is used in case of fire to extract smoke gases from the room. Smoke-free escape ways increase the chances to rescue people in case of fire.In the serially available version the hatch is intended for emergency use only (without EMC protection, without PTC in motor).Dual-use additional safety elements are necessary to reduce risks associated with hatch closing. The product has been tested up to Re 10000 cycles of open-close. For installation on the tops of buildings with snow load SL 1000 (SL 1250 for size 1250) and wind suction load WL 1500, the casing consists of a double metal layer with mineral wool insulation. The hatch casing is constructed of ZM (ZnAlMg coated) steel, while the hatch cover is made of AlMg3. Service switches, separate for motor and actuator(s), are serially installed on the hatch casing. Separate power supply for the fan and hatch actuator(s) is required, with electrical connections located within the service switches. When selecting the AES exhaust air and smoke extraction control accessory, please consider the serial connecting capability of the fan's service switch (as per instructions). Higher connecting capability is available upon request. It is recommended to start the fan 20 seconds after starting the actuator for cover opening to ensure vertical exhaust of hot gases. For non-ducted appliances, a protective grid for the inlet is available as an accessory. When using inlet cone ESD-F, a short duct between the cone and MRH is required due to the cone's diameter. The maximum nominal power of the inserted fan is 37 kW.

Sertifikatai

Žalioji ventiliacija certification logo
Žalioji ventiliacija

Our very own environmental performance benchmark guides you toward the most sustainable solutions within our portfolio. Only products which meet a set of easily verifiable minimum requirements in terms of energy efficiency, indoor air quality, safety, and the like are entitled to receive the Green Ventiulation™ label.

Techninės specifikacijos

Techniniai duomenys

Gaminio pavadinimas
MRH 400-2-1.1-F400
Gaminio numeris
#9995300
400V 3~ 50Hz - Y (Star)
Nominalieji duomenys
Nominali įtampa400V
Dažnis50Hz
Fazės3~
El. galia (P1)1 313W
Įvesties galia kW1,313kW
Nominali galia (P2)1,1kW
Srovė2,4A
Apsisukimai per minute2 940apsk./min.
Oro srautasmaks 7 100m³/h
Maks. pratekančio oro temperatūra 120 min.400°C
Maks. pratekančio oro temperatūra-20 į 55°C
Garso duomenys
Garso slėgio lygis 10 m. atstumu61dB(A)
Garso slėgis 3 m atstumu (atviras laukas)71dB(A)
Garso slėgio lygis 4 m. atstumu69dB(A)
Apsauga / klasifikacija
Apsaugos klasėIP55
Variklio apsaugos klasėIP55
SertifikatasCPR 597958
EU standartasEN 12101-3
Duomenys pagal ErP
ErP atitiktisNot ErP relevant
Išmatavimai ir svoriai
Ortakio matmuo; apvalus, įtekėjimas400mm
Svoris259kg
Kita
Ortakio pajungimo tipasApskritas
Variklio tipasAC

Diagrama

Matmenys

MRH #9995300, Matmenys
TypeøDøD1n x M*AA1A2BB1B2GCHFHH1SH, ~SV, ~
MRH-AXC 400
4004508 x M8*1000747107010007471050106445012501410185800
*bolts

Specifikacijos

The Motorised Roof Hatch (MRH) unit is designed for the insertion of an axial smoke and heat extraction fan, with the motor positioned within the airflow. It has been rigorously tested and certified for the extraction of hot gases up to 400°C for 2 hours (F400) or as per the specifications of the installed fan. The serial version is intended solely for emergency use, opening via an actuator to enable vertical extraction in the event of a fire.This unit is suitable for installation on the roofs of buildings with snow load ratings of up to SL 1000 (or SL 1250 for size 1250) and wind suction load ratings of WL 1500. It is designed for surface mounting on flat roofs. The casing features a double metal layer with mineral wool insulation, with a wall thickness of 120 mm and a cover thickness of 150 mm. The hatch casing is constructed from ZM (ZnAlMg coated) steel, while the hatch cover is made of AlMg3.Service switches for both the motor and actuator are installed serially on the hatch casing, with electrical connections housed within these switches. It is recommended to start the fan 20 seconds after activating the actuator to open the cover, ensuring the vertical exhaust of hot gases. The inlet side connection conforms to Eurovent ½ standards, and an exhaust protective grid is included.     

Dokumentai

Elektros jungimai

Diagram 1 (connection of electric motor in the fan`s service switch)
Electric motor with P2<=4 kW in Y or D connection
Lock the switch in position ON to prevent unintended switch OFF (lock is not in scope of delivery)
Diagram 2 (connection of actuator in the actuator`s service switch)
* 24VDC (+30/-20%)
** NO/NC are intended to control position of actuator`s service switch (ON - OFF)
Warning: the control voltage 24VDC to open or close hatch cover should apply max. 6 minutes.
This is to ensure by control system (use actuator`s internal floating limit switches as indication of cover position to cut off the control voltage). More see instructions (current, intermittence).
The connection cable to service switch calculate with max. 1V voltage drop at max. load!
Operating mode for peak load at 25°C ambient: S2 1 min
Operating mode for continuous load at 40°C ambient: S3 5% (example: open in 30s, then wait 9min 30s)
Max. current of actuator(s) at SL 1000 (rated MRH load):
MRH 400-630: 4A
MRH 710-800: 6A
MRH 1000: 8A
MRH 1120-1250: 2x8A=16A
Diagram 3 (connection of actuator`s internal floating limit switches in the actuator`s service switch)
*** drawn position - closed hatch
1-2 opened, 2-3 closed in closed hatch position
1-2 closed, 2-3 opened in opened hatch position
1-2 closed, 2-3 closed in any intermediary position of the hatch cover
1-2, 4-5 opened, 2-3, 5-6 closed in closed hatch position (MRH 1120-1250 only)
1-2, 4-5 closed, 2-3, 5-6 opened in opened hatch position (MRH 1120-1250 only)
1-2, 4-5 closed, 2-3, 5-6 closed in any intermediary position of the hatch cover (MRH 1120-1250 only)
Potentialfree NC contacts, load capacity 24VDC/1A
Functions of the actuator`s service switch:
Position 0: stop (NO - opened contact, NC - closed contact) - SAFETY POSITION
Position 1: open hatch cover (NO - closed contact, NC - opened contact) - WARNING!
Position 2: close hatch cover (NO - opened contact, NC - closed contact) - DANGER!

Priedai

ESD-F 400 Perėjimas AXC
#305258 · for air handling units
148,00 €neįskaitant mokesčių
GFL-AR/AXC 400 flanšas
#8378 · for air handling units
33,00 €neįskaitant mokesčių