VBR100-50-2 Water heating bat

VBR

Duct heaters with rectangular connections and hot water as energy medium

  • Rectangular duct installation horizontaly or verticaly

  • Corrosion protected casing

  • Air tightness class C

  • Removable access panel for inspection and cleaning


VBR 100-50-2 Water heating bat#5470

Duct installation

The VBR water heating battery is designed for standard rectangular ducts and can be installed by using screws or guide connections in horizontal or vertical position with an optional direction of airflow.

High air tightness

VBR duct heaters meet air tightness class C as per EN 15727, which ensures that the heated air reaches its destination and does not leak out of the ventilation system that saves both energy and money.

Robust design

Casing of VBR made of Zinc Magnesium-coated sheet steel (ZM 200) to provide high corrosion protection.

Easy maintenace

The duct heater is also equipped with nipples for draining and venting as well as an internally threaded connection for installation of antifreeze sensors.

Application: The VBR water heating battery is designed to use hot water as an energy medium and is used to heat up the ventilation air in a ventilation system with rectangular ducts.

Design: Casing made of Zinc Magnesium-coated sheet steel, ZM 200. Coil with copper pipes and pipe connections as well as aluminium fins. Duct connections are fitted with standard 20 mm flanges. VBR duct heaters meet air tightness class C as per EN 15727. The VBR duct heater is also equipped with nipples for draining and venting as well as an internally threaded connection for installation of antifreeze sensors.

Installation: Can be installed in a horizontal or a vertical duct with the air flow in any direction. It is also designed to be fixed to the rectangular duct system with screws or guide connections. If the VBR water heating battery is being used in cold conditions, then it should be fitted with a frost protection device with a sensor to reduce the risk of damage from freezing.

Operating Data: Maximum operating temperature of 150 °C and a maximum operating pressure of 1,0 MPa (10Bar). All the coils are pressurised and leak tested.

Control: Unit capacity can be controller on demand by using recommended acccessories - controllers, various sensors, vavles and actuators to provide regulation of the room or supply air temperature.

Maintenance: The water heating battery is fitted with a removable cover to facilitate easy cleaning and maintenance. The heat exchanger must be cleaned regularly in order to retain the best performance from the heater. Cleaning is facilitated by using a mild detergent. An effective filter is recommended in the system to reduce maintenance work.

Tech specs

Technical Data

Article name
VBR 100-50-2 Water heating bat
Article number
#5470
Default
Nominal data
Maximum operating temperature150°C
Dimensions and weights
Duct dimension, inlet (height x width)500 x 1,000mm
Duct dimension, outlet (height x width)500 x 1,000mm
Weight15.8kg
Others
Duct cooler/heaterHeater coil, water
Maximum operating pressure at water temperature 100°C1,600,000Pa
Maximum operating pressure at water temperature 150°C1,000,000Pa
Duct connection typeRectangular

Performance

Operations

 
VBR
 
Water temp. (in/out)
Air
Flow (m3/h)
 
Pressure drop (Pa)
 
ΔT
 
Capacity (kW)
Water
Flow (l/s)
 
Pressure drop (kPa)
40-20-260/40ºC400918.52.70.030.5
 
 10004812.74.60.061
40-20-4
 4001829.54.30.050.5
 
 10009619.57.10.090.5
40-20-2
80/60ºC400932.84.70.061
 
 10004824.58.90.112
40-20-4
 4001846.36.70.080.5
 
 10009638.914.00.171
50-25-2
60/40ºC600821.74.70.061
 
 12002918.27.90.102
50-25-4
 6001633.17.20.090.5
 
 12005928.412.30.151
50-25-2
80/60ºC600836.57.90.102
 
 12002928.612.40.154
50-25-4
 6001654.511.80.141
 
 12005945.919.90.243
50-30-2
60/40ºC8001018.25.30.060.5
 
 20005413.59.80.121
50-30-4
 8002032.59.40.111
 
 200010927.219.70.242
50-30-2
80/60ºC8001033.69.70.121
 
 20005424.317.50.212
50-30-4
 8002053.815.50.191
 
 200010941.730.10.374
60-30-2
60/40ºC10001119.26.90.081
 
 25005815.413.90.172
60-30-4
 10002234.112.30.151
 
 250011728.225.50.314
60-30-2
80/60ºC10001134.312.40.151
 
 25005824.422.10.274
60-30-4
 10002253.919.50.242
 
 250011741.837.80.467
60-35-2
60/40ºC12001118.78.10.100.5
 
 30006115.016.30.202
60-35-4
 12002334.214.80.181
 
 300012328.130.40.374
60-35-2
80/60ºC12001133.914.70.181
 
 30006124.126.10.323
60-35-4
 12002353.623.20.283
 
 300012341.545.00.558
70-40-2
60/40ºC20003120.114.50.181
 
 40009416.023.20.281
70-40-3
 20004624.717.80.220.5
 
 400013921.130.50.371
70-40-2
80/60ºC20003134.725.10.311
 
 40009425.136.30.443
70-40-3
 20004645.432.80.401
 
 400013934.449.70.612
80-50-2
60/40ºC25002521.119.00.230.5
 
 50007717.231.10.381
80-50-3
 25003728.025.30.310.5
 
 500011324.043.40.521
80-50-2
80/60ºC25002536.833.30.411
 
 50007726.948.60.592
80-50-3
 25003748.443.70.531
 
 500011337.167.00.822
100-50-2
60/40ºC30002324.826.90.321
 
 60007218.440.00.482
100-50-3
 30003532.335.00.421
 
 600010625.655.40.672
100-50-2
80/60ºC30002338.441.60.512
 
 60007228.261.10.754
100-50-3
 30003550.154.30.662
 
 600010638.783.81.024

Dimensions

VBR #5470, Dimensions
F=
Thread G 1/4
G=
Airing
H=
Water out
I=
Connection for immersion sensor
J=
Water in
K=
Draining
Ac/c ABc/c BE
VBR 40-20-2
438420238220R¾''
VBR 50-25-2
538520288270R¾''
VBR 50-30-2
538520338320R¾''
VBR 50-40-2
538520438420R¾''
VBR 60-30-2
638620338320R¾''
VBR 60-35-2
638620388370R¾''
VBR 70-40-2
738720438420R 1''
VBR 80-40-2
838820438420R 1''
VBR 80-50-2
838820538520R 1''
VBR 100-50-2
10381020538520R 1''
 
     
 
Ac/c ABc/c BE
VBR 40-20-4
438420238220R¾''
VBR 50-25-4
538520288270R¾''
VBR 50-30-4
538520338320R 1''
VBR 50-40-4
538520438420R 1''
VBR 60-30-4
638620338320R 1''
VBR 60-35-4
638620388370R 1''
 
     
 
Ac/c ABc/c BE
VBR 70-40-3
738720438420R 1''
VBR 80-50-3
838820538520R 1''
VBR 100-50-3
10381020538520R 1''
VBR 120-60-3
12381220638620R 1¼"