KV100 M sileo

KV Circular Duct Fans

High-efficient wall-mounted duct fan

  • Available with AC and EC motors

  • Mounted on wall or ceiling

  • Reliable and airtight

  • Noise and energy optimized impeller

KV 100 M sileo#1205
Frequency: 50/60 Hz

Flexibility

The KV fans are intended to use for supply or extract air, designed to be installed in wall or ceiling and are highly flexible according to your demands. This ensures that the fans can be used in a variety of commercial and domestic applications.

Reliability

The unit’s airtight casing and corrosion resistance permits demanding indoor use. The combination of reliable casing and motor construction ensures, to minimize the need for maintenance of the fans and allows long continuous operation.

Performance

Noise optimized radial impeller together with high efficient external rotor motor are designed to ensure high-level performance to minimize power consumption and maximize efficiency.

Accessories

KV fans can be selected together with variety types of accessories as fast clamps, heaters, filters, dampers, etc.

Systemair Accessories – the perfect match!

Save time in design and installation while ensuring the most optimal ventilation solutions for your project.

Featured accessories for your KV-fan

FK
Mounting clamps for circular duct
ECBasic
Controller series with 0-10V analog output signal
LDC
Easily-fitted silencer for circular ducts where noise reduction is paramount

Certifications

Loading...

Tech specs

Features

Construction

Casing made of galvanised sheet steel, corrosion class C3 is fully air tight class C according to EN1751. The fans are equipped with an external terminal box with protection class IP55.

Impeller

KV fans use backward curved radial impellers. These are from lightweight, hard-wearing fiberglass reinforced polyamide, dynamically balanced and paired with corresponding external rotor motors.

Motor

Depending on type, KV fans are equipped with AC or high efficient EC external rotor motors. All motors are suitable for 50Hz and 60Hz.

Motor protection

Fans with AC motors have integrated thermal protection with manual (electrical) reset. Size 100 and 125 has an impedance motor protection.

Fans with EC motors have integrated electronic thermal protection including locked-rotor protection and soft-start.

Control

EC motor with built-in potentiometer to adjust working point can be also controlled by external signal 0-10V.

AC motor can be controlled by 5-step or stepless speed regulator.

Installation

KV fans can be fixed in the necessary position on site (wall, ceiling) by using 4 screws according to the manual. Any position of the terminal box is possible. All models share a 25 mm spigot connection which is perfectly designed to connect circular duct by fast clamps preventing vibration to the duct.

Installation can be combined with filter boxes, sound attenuators and other mechanical accessories from recommended list.

Technical Data

Article name
KV 100 M sileo
Trade name
Systemair
Article number
#1205
230V 1~ 50Hz
Nominal data
Voltage (nominal)230V
Frequency50Hz
Phases1~
Input power29W
Input power kW0.029kW
Input current0.17A
Impeller speed2,465rpm
Air flowmax 56L/s
Temperature of transported airmax 70°C
Max temperature of transported air, when speed controlled70°C
Sound data
Sound pressure level at 3m (20m² Sabin)32dB(A)
Protection/Classification
Enclosure class, motorIP44
Insulation classB
Data according to ErP
Energy class, Basic unitF
Energy class, Local demandC
ErP readyErP 2018
Dimensions and weights
Duct dimension; Circular, inlet100mm
Duct dimension; Circular, outlet100mm
Weight2.1kg
Others
Duct connection typeCircular
Motor typeAC

Ecodesign

230V 1~ 50Hz
Basic unit
ErP compliance2018Basic unit
SEC Average-7.48kWh/(m².a)
SEC Cold-23.88kWh/(m².a)
SEC Warm1.92kWh/(m².a)
SEC ClassF
Unit categoryRVU
Unit typeUVU
DriveExternal MSD or VSD
Heat recovery typeNone
Temperature ratio (UVU)Not applicable
qv max89m³/h
P max28W
Sound power (LWA)28dB(A)
qv ref0.0172m³/s
Ps ref50Pa
SPI0.309W/(m³/h)
CTRL1
MISC1.1
x-value1.5
External Leakage5%
AEC average387kWh
AHS Cold387kWh
AEC warm387kWh
AHS Average17kWh/a
AHS Warm8kWh/a
Units with local demand control
ErP compliance2018Units with local demand control
SEC Average-23.23kWh/(m².a)
SEC Cold-50.29kWh/(m².a)
SEC Warm-7.73kWh/(m².a)
SEC ClassC
Unit categoryRVU
Unit typeUVU
DriveExternal MSD or VSD
Heat recovery typeNone
Temperature ratio (UVU)Not applicable
qv max89m³/h
P max28W
Sound power (LWA)28dB(A)
qv ref62m³/s
Ps ref50Pa
SPI0.309W/(m³/h)
CTRL0.65
MISC1.1
x-value1.5
External Leakage5%
AEC average203kWh
AEC cold203kWh
AEC warm203kWh
AHS Average28kWh/a
AHS Cold55.4kWh/a
AHS Warm13kWh/a

Performance

Dimensions

KV #1205, Dimensions
A
5
B
143
C
26
ØD
99
ØE
218
F
40
G
254
H
284

Documentation

BIM

Loading...










Wiring

KV #1205, Wiring

BU = Blue

BK = Black

GY = Green/Yellow