Water coil SAVE VTR300/350

Water coil SAVE VTR

Water heating battery with frost protection sensor

  • Frost protection sensor 

  • Max operating temperature 125 °C 

  • Max operating pressure 0,8 MPa (8 Bar) 

  • Installed inside the SAVE unit


Water coil SAVE VTR 300/350#141700
£ 218.86excl. tax
or create account to buy online

Water-heating battery

The water coil is a water-heating battery for heating up the air to the desired temperature. 


Installed inside the unit

The water-heating battery should be installed inside the SAVE unit, replacing the already-mounted electrical heater. 


Max operating temperature

The water coil has a maximum operating temperature of 125 °C and a maximum operating pressure of 0,8 MPa (8 Bar). 


Frost protection

The water-heating battery is equipped with a frost protection sensor that lets you know when the water temperature is too low.


Water coil SAVE VTR 300/350 #141700

Water-heating battery for heating up the air to desired temperature in SAVE VTR 300 unit with SAVE control system.The water-heating battery should be installed inside the unit, replacing the already mounted electrical re-heater.Max operating temperature 125 °CMax operating pressure 0,8 MPa (8 Bar)2-rows battery

Tech specs

Technical Data

Article name
Water coil SAVE VTR 300/350
Article number
#141700
Default
Dimensions and weights
Weight1.13kg

Performance

Operations

Inlet T air , °C12141618
Air flow (m3/s)
0,08330,08330,08330,0833
Outlet T air at T water 60/40, °C
21,9323,0324,0524,9
Pressure drop (Pa)
25,8526,0426,2326,42
Water flow rate (l/s)
0,0120,0110,00990,0085
Water speed (m/s)
0,170,160,140,12
Pressure drop (kPa)
0,420,360,30,23
Power (kW)
1,010,920,820,7
Outlet T air at T water 55/30, °C
18,0719,5521,0322,5
Pressure drop (Pa)
25,6625,8726,0826,3
Water flow rate (l/s)
0,0060,00540,00490,0044
Water speed (m/s)
0,090,080,070,06
Pressure drop (kPa)
0,130,110,10,06
Power (kW)
0,620,560,510,46
Outlet T air at T water 60/30, °C
18,3619,8321,3122,78
Pressure drop (Pa)
25,6825,8826,126,31
Water flow rate (l/s)
0,00520,00480,00430,0039
Water speed (m/s)
0,070,070,060,06
Pressure drop (kPa)
0,10,090,080,06
Power (kW)
0,640,590,540,49
Outlet T air at T water 90/70, °C
34,836,0637,3138,56
Pressure drop (Pa)
26,4726,6726,8727,08
Water flow rate (l/s)
0,0280,0270,0270,026
Water speed (m/s)
0,410,390,380,37
Pressure drop (kPa)
1,641,551,461,38
Power (kW)
2,312,242,172,09
Outlet T air at T water 35/25, °C
15,9317,418,8820,35
Pressure drop (Pa)
25,5625,7625,9826,2
Water flow rate (l/s)
0,00960,00830,0070,0058
Water speed (m/s)
0,140,120,10,08
Pressure drop (kPa)
0,320,250,190,14
Power (kW)
0,40,350,290,24

Dimensions

Water coil SAVE VTR #141700, Dimensions
*
Bleeding valve
A
Outlet
B
Inlet
FPS
Frost protection sensor

Documentation