Water heating battery with frost protection sensor
Frost protection sensor
Max operating temperature 125 °C
Max operating pressure 0,8 MPa (8 Bar)
Installed inside the SAVE unit
The water coil is a water-heating battery for heating up the air to the desired temperature.
The water-heating battery should be installed inside the SAVE unit, replacing the already-mounted electrical heater.
The water coil has a maximum operating temperature of 125 °C and a maximum operating pressure of 0,8 MPa (8 Bar).
The water-heating battery is equipped with a frost protection sensor that lets you know when the water temperature is too low.
Water coil SAVE VTR 300/350 #141700
Water-heating battery for heating up the air to desired temperature in SAVE VTR 300 unit with SAVE control system.The water-heating battery should be installed inside the unit, replacing the already mounted electrical re-heater.Max operating temperature 125 °CMax operating pressure 0,8 MPa (8 Bar)2-rows battery
Default | |||
---|---|---|---|
Dimensions and weights | |||
Weight | 1.13 | kg |
Inlet T air , °C | 12 | 14 | 16 | 18 |
Air flow (m3/s) | 0,0833 | 0,0833 | 0,0833 | 0,0833 |
Outlet T air at T water 60/40, °C | 21,93 | 23,03 | 24,05 | 24,9 |
Pressure drop (Pa) | 25,85 | 26,04 | 26,23 | 26,42 |
Water flow rate (l/s) | 0,012 | 0,011 | 0,0099 | 0,0085 |
Water speed (m/s) | 0,17 | 0,16 | 0,14 | 0,12 |
Pressure drop (kPa) | 0,42 | 0,36 | 0,3 | 0,23 |
Power (kW) | 1,01 | 0,92 | 0,82 | 0,7 |
Outlet T air at T water 55/30, °C | 18,07 | 19,55 | 21,03 | 22,5 |
Pressure drop (Pa) | 25,66 | 25,87 | 26,08 | 26,3 |
Water flow rate (l/s) | 0,006 | 0,0054 | 0,0049 | 0,0044 |
Water speed (m/s) | 0,09 | 0,08 | 0,07 | 0,06 |
Pressure drop (kPa) | 0,13 | 0,11 | 0,1 | 0,06 |
Power (kW) | 0,62 | 0,56 | 0,51 | 0,46 |
Outlet T air at T water 60/30, °C | 18,36 | 19,83 | 21,31 | 22,78 |
Pressure drop (Pa) | 25,68 | 25,88 | 26,1 | 26,31 |
Water flow rate (l/s) | 0,0052 | 0,0048 | 0,0043 | 0,0039 |
Water speed (m/s) | 0,07 | 0,07 | 0,06 | 0,06 |
Pressure drop (kPa) | 0,1 | 0,09 | 0,08 | 0,06 |
Power (kW) | 0,64 | 0,59 | 0,54 | 0,49 |
Outlet T air at T water 90/70, °C | 34,8 | 36,06 | 37,31 | 38,56 |
Pressure drop (Pa) | 26,47 | 26,67 | 26,87 | 27,08 |
Water flow rate (l/s) | 0,028 | 0,027 | 0,027 | 0,026 |
Water speed (m/s) | 0,41 | 0,39 | 0,38 | 0,37 |
Pressure drop (kPa) | 1,64 | 1,55 | 1,46 | 1,38 |
Power (kW) | 2,31 | 2,24 | 2,17 | 2,09 |
Outlet T air at T water 35/25, °C | 15,93 | 17,4 | 18,88 | 20,35 |
Pressure drop (Pa) | 25,56 | 25,76 | 25,98 | 26,2 |
Water flow rate (l/s) | 0,0096 | 0,0083 | 0,007 | 0,0058 |
Water speed (m/s) | 0,14 | 0,12 | 0,1 | 0,08 |
Pressure drop (kPa) | 0,32 | 0,25 | 0,19 | 0,14 |
Power (kW) | 0,4 | 0,35 | 0,29 | 0,24 |