FDS_EX Rectangular Fire Dampers

Fire damper modified for potentially explosive atmospheres following also the 2014/34/EU directive.

  • Suitable for Gas and Dust explosive atmosphere

  • Inspection opening built-in

  • Tightness class 3C as standard

  • Great variety of installations rated up to EI120S


Atex class

Group II, category 2 G and 2 D

Manual or Actuator Mechanism

Systemair manufactured manual mechanism with conductive plastic is made to be spark free.

Be Efficient

Tightness class above the required limit of CE harmonized standard

Inspection openings

All FDS...EX rectangular dampers of sizes greater than 200x200 mm come complete with two inspection openings. 

Atex fire dampers represent passive fire protection, designed with the help of compartmentalization to prevent the spread of toxic gases, smoke and fire. Standard fire dampers are designed and certified in accordance with EN 15650 and tested for EIS criteria according to EN 1366–2. Fire dampers together with their installation form an inseparable part of a fire resistivity rating.

This Atex version is modified by the 2014/34/EU directive, which sets out the technical requirements for equipment and protective systems intended for use in potentially explosive atmospheres.

Against the ignition

  • of gas, explosion group IIB,

  • of dust, explosion group IIIB

Equipment Protection Level

Db and Gb

According to EN ISO 80079-36.2016

Temperature class

  • T85 °C...T100 °C for Db

  • T6…T5 for Gb