MUB CAV/VAVMUB-CAV/VAV 100 630EC

MUB CAV/VAV Insulated duct fans

Powerful centrifugal fans with integrated CAV/VAV sensor-control module

  • Integrated sensor-control module

  • Easy adjustment of the operation mode if needed

  • All sizes pre-wired, pre-adjusted and factory tested

  • Acoustic and thermal insulation 30 mm

  • Flexible airflow direction due to removable panels

  • Indoor and outdoor installation

  • Modular system of accessories

  • Available with EC motors for 50 and 60Hz

MUB-CAV/VAV 100 630EC#230508
Frequency: 50/60 Hz

Smart Technology

The MUB CAV/VAV is equipped with a sensor-control module and complete connection for constant air flow. The system is completely pre-wired for easy operation and installation. Depending on the adjusted operation mode the controller can be used as sensor- or control module.

It is possible to choose between multiple operation modes, from constant pressure, constant air volume (factory set), or just display data.

Flexibility

The MUB CAV/VAV fans are intended to use for supply or extract air, designed to be installed in any position.

The MUB fans are designed for straight through airflow but can easily be rebuilt due to removable panels for 90° air discharge. The construction of the casing and thermal insulation permits outdoor and indoor use.

Performance

High performence impeller together with high efficient motors are designed to ensure high-level performance to minimize power consumption and maximize efficiency.

Modularity

Thanks to variety types of accessories as flexible connections, dampers, roof, base frame, etc. it is easy to design any ventilation system according to your demand.

By using special modular systems, where some accessories as heaters, coolers, silencers, filters or carbon filters are built-in in the same type of casing, you can even design a simple supply or exhaust air handing unit.

Certifications

Loading...

Tech specs

Features

Construction

The casing consists of a corrosion-resistant aluminium frame with fibreglass reinforced plastic corners of PA6; highly shock-resistant. Panels made of double skin galvanized sheet steel with 30 mm acoustic and thermal rockwool insulation.

The MUB CAV/VAVfans are designed for straight through airflow but can easily be rebuilt due to removable panels for 90° air discharge

Impeller

The MUB CAV/VAV fans use radial impeller with backward curved blades. These are made out of high-performance composite material or aluminum, dynamically balanced and paired with corresponding EC external rotor motors.

Motor

MUB CAV/VAV fans are equipped with EC motors. Motors are suitable for 50Hz and 60Hz.

Motor protection

EC motors have an integrated electronic thermal protection including locked-rotor protection and soft-start.

Control

The "constant pressure kit" which is included in the MUB-CAV/VAV the operation mode can be changed from CAV to VAV (constant pressure).

The fan is directly controlled with the 0-10V output signal of the sensor-control module.

EC motors, depending on the type are also equipped with ModBus communication or alarm signal.   

Installation

The MUB CAV/VAV fans can be installed in any position indoor and together with weather protection roof also outdoor. With mounted base frame the MUB fans can stand on floor.  For preventing vibration to the duct it is recommended to use flexible connections.

Technical Data

Article name
MUB-CAV/VAV 100 630EC
Trade name
Systemair
Article number
#230508
400V 3~ 50/60Hz - 90° air flow
Nominal data
Voltage (nominal)400V
Frequency50; 60Hz
Phases3~
Input power3,099W
Input power kW3.099kW
Input current5.01A
Impeller speed1,339rpm
Air flowmax 19,205m³/h
Temperature of transported airmax 70°C
Max temperature of transported air, when speed controlled70°C
Protection/Classification
Enclosure class, motorIP55
Insulation classF
Data according to ErP
ErP readyErP 2018
Dimensions and weights
Weight136kg
Others
Motor typeEC

Ecodesign

400V 3~ 50/60Hz - 90° air flow
Product
Trade nameSystemair
Product nameMUB-CAV/VAV 100 630EC
Ecodesign
ErP compliance2018
Unit categoryNRVU
DriveIntegrated VSD
Unit typeUVU
Heat recovery typeNone
Temperature ratio (UVU)Not applicable
qv nom3.2008m³/s
P nom3.072kW
Ps nom622Pa
Fan efficiency64.8%
External Leakage5%
Sound power (LWA)58dB(A)

Performance

Acoustic

The Level of Casing-Breakout-Noise depends on the quality of shielding the acoustic inlet and outlet noises.

The shown Level of Casing-Breakout-Noise will be reached only in case of 100 % shielding the acoustic inlet and outlet noise and a correspondingly low environment noise.

Dimensions

MUB-CAV/VAV 100
630/710
□A
1020
□B
1020
□C
920
□D
878
E
21
F
1106
MUB CAV/VAV #230508, Dimensions

Documentation

BIM

Loading...










Wiring

MUB CAV/VAV #230508, Wiring
.
Function / assignment
L1, L2, L3
Power, supply, see name plate
PE
Protective earth
RSA
RS485 interface for MODBUS, RSA
RSB
RS485 interface for MODBUS, RSB
GND
Reference ground for control interface
IO1
Function: Disable-InputDigital Input- Inactive: Pin open or applied voltage < 1,5 VDC -> fan runds according to the set 0-10 V- setpoint (IO2)- Active: applied voltage 3,5-50 VDC -> fan stops- Reset- Function: Error - reset when the status changes from "inactive" to "active"
IO2
Function: SetpointAnalog input 0-10 V / PWM, Ri = 100kΩ
IO3
Function: Actual speedAnalog output 0-10 V, max.5 mAOutput is a speed proportional voltage.- 10 V corresponds max. rpm- 5 V corresponds max. rpm / 2(n = 1.02 * nMax)
Vout
Function: Voltage output10 VDC, short-circuit-proof (Pmax = 800 mW)
COM
Function: Status relayStatus relay, floating status contact, contact rating 250 VAC / 2 A; min. 10mA
NC
Function: Status relayStatus relay, floating status contact, open in the event of an error and in the de-energized state
LED
Function: Status reports- green = operational readiness- orange = warning- red = error
X1
Terminal box with connected potentiometer* Included in the scope of delivery for fans with EC motor without external control.
MUB CAV/VAV #230508, Wiring
.
.
RD
Red
BU
Blue
YE
Yellow
MUB CAV/VAV #230508, Wiring