CO2 and temperature transmitter suitable for wall mounting
Wall sensor
Good long-term stability
RBC algorithm
Very high accuracy
The CO2 transmitter are intended for wall mounting in HVAC systems. The sensors are mounted in the cover part of the casing.
Cover of the seonsors is easy to detach from the back by means of snap-in grips and detachable terminals. Furthermore, no cables have to be disconnected, simplifying service and replacement.
The transmitter is equipped with a function that can be activated to achieve a more stable CO2 level in a room that is not used for parts of the day.
The transmitters have automatic calibration. This means that manual recalibration is not required during the lifetime of the transmitter.
CO2 wall sensors are transmitters combining both CO2 levels and temperature in the same casing. Working range for CO2 sensor is 0...2000 ppm and output signal 0...10 V, and working range for PT1000 temperature sensor is 0...50°C.The transmitters have automatic calibration meaning that manual recalibration is not required during the lifetime of the transmitter. The sensors are mounted in the cover part of the casing and the cover is easy to detach to facilitate easy mounting. No cables have to be disconnected making both servicing and replacement simple.
The transmitter is equipped with a function that can be activated to get a more stable CO2 level in a room that is not used for parts of the day. The CO2 concentration is measured using infrared light that measures the absorption in gases. It has a reference measuring system that compensates values in relation to changes in light intensity. This provides very high accuracy, a short response time and excellent long-term stability. It provides exact identification of the detected gas and has a low risk of contamination.
24V 50/60Hz | |||
---|---|---|---|
Nominal data | |||
Voltage (nominal) | 24 | V | |
Frequency | 50; 60 | Hz | |
Input power | 3 | W | |
Input power kW | 0.003 | kW | |
Current, circuit breaking relay | 1 | A | |
Protection/Classification | |||
Enclosure class | IP30 | ||
Controller and Sensors | |||
Permitted humidity, non-condensing | 0 to 90 | %RH | |
Ambient and duct temperature | |||
Permitted ambient temperature | -5 to 55 | °C | |
Working range | 0...2000 ppm | ||
Switching capacity | 50V AC / 60V DC | ||
Accuracy | < ± (50 ppm +2% of measuring value) | ||
Dimensions and weights | |||
Weight | 0.11 | kg |