EC-Basic-CO2 and temperature #24808
• Simple to install, connect and set up• 50/60HZ mains option• Can be used with all 220V single phase and 380V three phase EC fans• Built in sensors• Conforms to CE standards EN 60730-1, EN 61000-6-3, EN 61000-6-1• Demand control made simpleThe controller compares room temperature with an adjustable set point (knob) and regulates a 0..10 V proportional integral INTERNAL 1 SIGNAL in direct or reverse action based on jumper JP1 setting:JP1 closed 1-2 = heating (reverse action)JP1 closed 2-3 = cooling (direct action)The controller compares also CO2 with an adjustable set point (SW3) and regulates a 0..10 V proportional INTERNAL 2 SIGNAL in direct action.The output signal applied to a ventilator is the maximum between INTERNAL 1 SIGNAL and INTERNAL 2 SIGNAL.The range for temperature knob set point is from 5 to 30°C
50/60Hz | |||
---|---|---|---|
Nominal data | |||
Rated voltage | 85 to 265 | V | |
Frequency | 50; 60 | Hz | |
Input power | 2 | W | |
Input power kW | 0.002 | kW | |
Temperature | -20 to 50 | °C | |
Temperature setpoint | 5 to 30 | °C | |
Protection/Classification | |||
Enclosure class | IP30 | ||
Dimensions and weights | |||
Weight | 0.147 | kg | |
Others | |||
CO2 measurement | 0 to 2,000 | ppm |