Diagram 2 (connection of actuator in the actuator`s service switch) |
* 24VDC (+30/-20%)
|
** NO/NC are intended to control position of actuator`s service switch (ON - OFF)
|
Warning: the control voltage 24VDC to open or close hatch cover should apply max. 6 minutes.
|
This is to ensure by control system (use actuator`s internal floating limit switches as indication of cover position to cut off the control voltage). More see instructions (current, intermittence).
|
The connection cable to service switch calculate with max. 1V voltage drop at max. load!
|
Operating mode for peak load at 25°C ambient: S2 1 min
|
Operating mode for continuous load at 40°C ambient: S3 5% (example: open in 30s, then wait 9min 30s)
|
Max. current of actuator(s) at SL 1000 (rated MRH load):
|
MRH 400-630: 4A
|
MRH 710-800: 6A
|
MRH 1000: 8A
|
MRH 1120-1250: 2x8A=16A
|
Diagram 3 (connection of actuator`s internal floating limit switches in the actuator`s service switch)
|
*** drawn position - closed hatch
|
1-2 opened, 2-3 closed in closed hatch position
|
1-2 closed, 2-3 opened in opened hatch position
|
1-2 closed, 2-3 closed in any intermediary position of the hatch cover
|
1-2, 4-5 opened, 2-3, 5-6 closed in closed hatch position (MRH 1120-1250 only)
|
1-2, 4-5 closed, 2-3, 5-6 opened in opened hatch position (MRH 1120-1250 only)
|
1-2, 4-5 closed, 2-3, 5-6 closed in any intermediary position of the hatch cover (MRH 1120-1250 only)
|
Potentialfree NC contacts, load capacity 24VDC/1A
|
Functions of the actuator`s service switch:
|
Position 0: stop (NO - opened contact, NC - closed contact) - SAFETY POSITION
|
Position 1: open hatch cover (NO - closed contact, NC - opened contact) - WARNING!
|
Position 2: close hatch cover (NO - opened contact, NC - closed contact) - DANGER!
|