CE / CTCE 140 M-160 Centrifugal Fan
04080120160200240280320360400m³/h0100200300400Pa80V105V130V160V230V240291
Advanced calculation

CE / CT Centrifugal Fans

Compact and powerful fan for your professional environment

  • High-Performance

  • Compact deisign

  • Simple installation in any position

  • Maintenance-free and reliable

CE 140 M-160 Centrifugal Fan#1529
Frequency: 50 Hz

High performance

The CE/CT series of centrifugal fans are designed for indoor use with stable power performance for extract or supply air.

Compact design

The CE/CT fan has a compact form factor and can be installed in any required position. This supports various applications (commercial, industrial and residential).

Certifications

Ecodesign (ErP) compliant certification logo
Ecodesign (ErP) compliant

Compliant with today’s and tomorrow’s European Union rules and requirements for energy labelling and ecodesign for Energy-related Products (ErP).

Tech specs

Features

Construction

CE/CT fan casing made of galvanised sheet steel, corrosion class C3. Shape of the casing designed to obtain high efficiency.

CE fans are equipped with terminal box IP44 to simplify wiring process on site. CT fans are equipped with cable to connect to the external terminal box (separate accessory).

Impeller

Single inlet radial impellers with forward curved blades. Made of lightweight PP for sizes 125/160 and galvanised sheet steel for bigger sizes. All impellers dynamically balanced and paired with corresponding external rotor motors.

Motor

CE/CT fans are equipped with AC external rotor motor, insulation class B. All motors are supported by long-life ball bearings.

Motor protection

CE Fans have integrated thermal protection with manual (electrical) reset.

CT Fans have integrated thermal contact with external leads for connection to a motor protection device (separate accessory).

Control

All fans are controlled by 5-step or stepless speed regulator provided as accessory. Speed regulation can be combined with timer, thermostat, hygrostat, etc. by using wide range of electrical accessories.

Installation

Mounting of the CE/CT fans possible indoor in any mounting position.

CE models used standard inlet and outlet flanges to maximise adaptability with corresponding FK fast clamps.

Technical Data

Article name
CE 140 M-160 Centrifugal Fan
Trade name
Systemair
Article number
#1529
230V 1~ 50Hz
Nominal data
Voltage (nominal)230V
Frequency50Hz
Phases1~
Input power125W
Input power kW0.125kW
Input current0.54A
Impeller speed1,807rpm
Air flowmax 436m³/h
Capacitance of capacitor4µF
Temperature of transported airmax 65°C
Max temperature of transported air, when speed controlled65°C
Sound data
Sound pressure level at 3m (20m² Sabin)42dB(A)
Protection/Classification
Enclosure class, motorIP44
Insulation classB
Data according to ErP
Energy class, Basic unitF
Energy class, Local demandC
ErP readyErP 2016; ErP 2018
Dimensions and weights
Duct dimension; Circular, inlet160mm
Duct dimension; Circular, outlet160mm
Weight3.1kg
Others
Duct connection typeCircular
Motor typeAC

Ecodesign

230V 1~ 50Hz
Basic unit
ErP compliance2016Basic unit
SEC Average-9.1kWh/(m².a)
SEC Cold-25.5kWh/(m².a)
SEC Warm0.3kWh/(m².a)
SEC ClassF
Unit categoryRVU
Unit typeUVU
DriveExternal MSD or VSD
Heat recovery typeNone
Temperature ratio (UVU)Not applicable
qv max385m³/h
P max114W
Sound power (LWA)42dB(A)
qv ref0.075m³/s
Ps ref50Pa
SPI0.258W/(m³/h)
CTRL1
MISC1.1
x-value1.5
External Leakage5%
AEC average322.6kWh
AHS Cold322.6kWh
AEC warm322.6kWh
AHS Average1,715.2kWh/a
AHS Warm775.6kWh/a
Units with local demand control
ErP compliance2018Units with local demand control
SEC Average-24.1kWh/(m².a)
SEC Cold-51.1kWh/(m².a)
SEC Warm-8.6kWh/(m².a)
SEC ClassC
Unit categoryRVU
Unit typeUVU
DriveExternal MSD or VSD
Heat recovery typeNone
Temperature ratio (UVU)Not applicable
qv max387m³/h
P max114W
Sound power (LWA)42dB(A)
qv ref0.0752m³/s
Ps ref50Pa
SPI0.258W/(m³/h)
CTRL0.65
MISC1.1
x-value1.5
External Leakage5%
AEC average169.1kWh
AEC cold169.1kWh
AEC warm169.1kWh
AHS Average2,830kWh/a
AHS Cold5,536.2kWh/a
AHS Warm1,279.7kWh/a

Performance

Dimensions

CE / CT #1529, Dimensions

Documentation

Accessories

REU 1.5 Speed control
#5004 · 1.5A 1~ 5 step
RE 1,5 Speed control
#5000 · 1.5A 1~ 5 step
VKK-160 Back draft damper
#1625 · Louver shutter, PA, with steel box, for air handling units
IGK-160 Wall Grid
#1632 · Steel, bird screen, for air handling units
SG 160 Protection guard
#5608 · For air handling units
DTV500A
#96807 · DTV500A incl connection kit
Presence detector/IR24-P
#6995 · 6995 Presence detector/IR24-P
HR1 Room Humidistat
#215150 · SYSTEMAIR HR1 Humidistat RAL 9003
VBF 160 Water heating battery
#1731 · Duct heater 160 mm, water, with integrated filter
CB 160-2,1 230V/1 Duct heater
#5292 · Duct heater DN 160, electric, 2,1kW, 230V1~
CBMF 160-2,1 230V/1 Duct heate
#12244 · Duct heater DN 160, electric, 2,1kW, 230V1~, control/flow
VBC 160-2 Water heating batt
#5458 · Duct heater 160 mm, water, 2 rows
FGR 160 Filter cassette
#1809 · SYSTEMAIR FGR Panel filter box 160 dia
CB 160-1,2 230V/1 Duct heater
#5291 · Duct heater DN 160, electric, 1,2kW, 230V1~
CBM 160-2,1 230V/1 Duct heater
#5482 · Duct heater DN 160, electric, 2,1kW, 230V1~, control temp
CB 160-2,7 230V/1 Duct heater
#5382 · Duct heater DN 160, electric, 2,7kW, 230V1~
RSK-160 Back draft damper
#5601 · galvanized steel, for air handling units
LDC 160-900 Silencer
#5193 · Round, for air handling units
FFR 160 Filter cassette
#1770 · Filter cassette DN 160 mm, circular ducts
LDC 160-600 Silencer
#5192 · Round, for air handling units
LDC 160-300 Silencer
#53108 · Round, for air handling units
THS 160 Hood w.cover pl. black
#1839 · Roof cowl with cover, for air handling units
THB 160 Hood w.cover pl. black
#1764 · Roof cowl with cover, for air handling units
FK 160 Fast clamp
#1610 · FK Fast clamps each 160 dia, for air handling units