BKF-120 fans are used for ventilation in normal working conditions and can transport hot gases up to 120°C.
Continuous operation up to 120°C medium temperature
Casing made of zinc-magnesium coated steel (ZM)
Backward curved impeller made from steel and galvanized
Motor outside the air stream
Single speed IE3 motor
PTC serial built-in motor
Installation possible in all positions, flange connection 30 mm
Installation outside building or inside the building
Applications: malls, warehouses, kitchen exhaust...Generally suitable for ambient temperature -20 to +40°C (depending on specific motor load the permissible ambient temperature may be increased - on request). For speed control of single speed motors use a combination of frequency converter and appropriate filter to the motor side (sine or du/dt), respectively observe instructions. Not suitable for voltage control. Working points within the blue area of diagrams of single speed fans can be achieved with a frequency converter.
Nominal data | |||
---|---|---|---|
Voltage (nominal) | 400 | V | |
Frequency | 50 | Hz | |
Phases | 3~ | ||
Phases, supply fan | 3~ | ||
Motor circuit connection | D | ||
Input power | 8,700 | W | |
Input power kW | 8.7 | kW | |
Nominal power at shaft (P2) | 7.5 | kW | |
Starting current | 106 | A | |
Starting current (Y - D starting) | 35 | A | |
Input current | 15 | A | |
Impeller speed | 1,469 | rpm | |
Air flow | max 24,300 | m³/h | |
Temperature of transported air | max 120 | °C | |
Max temperature of transported air, when speed controlled | 120 | °C | |
Sound data | |||
Sound pressure level at 3m (20m² Sabin) | 74 | dB(A) | |
Sound pressure level at 3m (free field) | 60 | dB(A) | |
Sound pressure level at 4m (free field) | 62 | dB(A) | |
Protection/Classification | |||
Enclosure class, motor | IP55 | ||
Insulation class | F | ||
Data according to ErP | |||
ErP ready | ErP 2018 | ||
Dimensions and weights | |||
Duct dimension, inlet (height x width) | 800 | mm | |
Duct dimension, outlet (height x width) | 800 | mm | |
Weight | 192 | kg | |
Others | |||
Duct connection type | Rectangular | ||
Motor type | AC |
Product | |||
---|---|---|---|
Product name | BKF 710D4-XL-120°C | ||
Ecodesign | |||
ErP compliance | 2018 | ||
Unit category | NRVU | ||
Drive | External MSD or VSD | ||
Unit type | UVU | ||
Heat recovery type | None | ||
Temperature ratio (UVU) | Not applicable | ||
qv nom | 4.0556 | m³/s | |
P nom | 8.74 | kW | |
Ps nom | 1,319 | Pa | |
Fan efficiency | 61.2 | % | |
External Leakage | 0.1 | % | |
Sound power (LWA) | 81 | dB(A) |
BKF-120 thermo fansare intended to transport hot gases continuously up to 120°C during normal ventilation. Casing made of zinc-magnesium coated steel (ZM). Backward curved impeller made from steel and galvanised. Equipped with single speed IE3 motor outside the air stream. PTC serial built-in motor. Installation possible in all positions, flange connection 30 mm. Installation outside building or inside building. For speed control of single speed motors use combination of frequency converter and appropriate filter to motor side (sine or du/dt), respectively observe instructions.